Evidence map›Paper›PMID 39681587›Full record

ArticleScientific reports2024

Artificial intelligent fuzzy control and LAPO algorithm for enhancement LVRT and power quality of grid connected PV/wind hybrid systems.

Noura G El Sayed, Ali M Yousef, Gaber El-Saady, Meshari D Alanazi, Hamdy A Ziedan, Montaser Abdelsattar

Abstract read
In one paragraph

Article in Scientific reports, 2024. The graph could read no effect estimate from its abstract, so it casts no vote on the map. Cited by 6 papers.

0numbers the graph read from it
0cells of the map it votes in
6citing papers in PubMed
–field-weighted citation impact
1 · What the graph read from it

What it found

Each row is one number read from the abstract, on the scale the paper reported it, with its interval. Left of the dashed line favours the treatment, right favours the comparator. Under each row is the sentence it came from. New to these charts? A ten-minute tutorial.

The abstract states no effect estimate the extractor could read, or names no intervention and outcome on the map, so this paper lights no cell and moves no belief. It is still indexed, cited and linked below.

2 · The registry

The trial behind it

Trials whose registry record cites this paper, or whose number appears in the abstract. A trial that started after this paper was published is citing it as background, not reporting it.

Neither the registry nor the abstract names a trial number. If this is a trial report, that itself is worth knowing.

3 · Its place in the literature

Who cites it

6 citing papers in PubMed.

  1. Article
  2. Article
  3. Article
  4. Article
  5. Article
  6. Article
4 · The record

Corrections and comments

PubMed lists nothing against this paper. Absence here is not a guarantee, only a check that was made.

5 · Who and what money

Authors and funding

6 authors.

Noura G El SayedDepartment of Electrical Engineering, Faculty of Engineering, Assiut University, Assiut, 71516, Egypt.
Ali M YousefDepartment of Electrical Engineering, Faculty of Engineering, Assiut University, Assiut, 71516, Egypt.
Gaber El-SaadyDepartment of Electrical Engineering, Faculty of Engineering, Assiut University, Assiut, 71516, Egypt.
Meshari D AlanaziDepartment of Electrical Engineering, College of Engineering, Jouf University, Sakaka, 72388, Saudi Arabia.
Hamdy A ZiedanDepartment of Electrical Engineering, Faculty of Engineering, Assiut University, Assiut, 71516, Egypt.
Montaser AbdelsattarElectrical Engineering Department, Faculty of Engineering, South Valley University, Qena, 83523, Egypt. Montaser.A.Elsattar@eng.svu.edu.eg.

Funding

No grant is acknowledged in the PubMed record.

6 · The paper itself

Abstract

Low Voltage Ride Through (LVRT) is considered one of the main and serious problems facing the electrical grid. It occurs due to three-phase symmetric faults and asymmetric faults such as a double line to ground fault that applies in this system. This paper applies Static Synchronous Compensators (STATCOM) to improve the LVRT capability and dynamic performance of an electrical grid linked to a Photovoltaic (PV)/Wind hybrid system through grid disturbances. A hybrid power system containing a PV station that produces 1 MW and a wind farm from type Doubly Fed Induction Generator (DFIG) that produces 9 MW is connected to STATCOM with 48 pulses at PCC bus and energized load. It compensates reactive power to improve LVRT that occurred due to fault. The applied STATCOM controller adjusts the voltage of the PCC bus during an occuring fault on the grid by compensating reactive power. STATCOM is controlled by a Proportional-Integral-Derivative (PID) and is compared with STATCOM controlled by Artificial Intelligence Control (AIC)-based on Proportional-Integral Fuzzy Logic Control (PI FLC). The Lightning Attachment Procedure Optimization Algorithm (LAPO) optimization method is used to adjust the parameters of the PI controller to reduce error signals. A simulation model of the suggested hybrid power system has been performed using Matlab/Simulink. The simulation results of STATCOM proved powerful and the effectiveness of STATCOM with PI FLC in reducing voltage dip, compensating active power of wind and PV farm, protecting DC-link voltage of PV and wind from overvoltage and oscillation that happens at three-phase fault and double line to ground fault as compared with PID STATCOM in enhancement LVRT capability, and power quality.

Indexed as

Lightning attachment procedure optimization algorithm (LAPO)Low voltage ride through (LVRT)Photovoltaic (PV)Power qualityProportional–integral–derivative (PID) controllerProportional–integral fuzzy logic control (PI FLC)Static synchronous compensators (STATCOM)Wind

Identifiers

PMID39681587
PMCPMC11649785

What OpenQuestion holds

Textmetadata
LicenceCC BY
Read underepoch 390

Registered trials

None linked

Read under generation 80e0d062 · epoch 390. Bibliography from PubMed, PubMed Central and OpenAlex; grants from NIH RePORTER; trial links from ClinicalTrials.gov; estimates, votes and beliefs from the OpenQuestion graph.