ArticleHealthcare (Basel, Switzerland)2021
Performance Improvement of a Negative-Pressurized Isolation Room for Infection Control.
Article in Healthcare (Basel, Switzerland), 2021. The graph could read no effect estimate from its abstract, so it casts no vote on the map. Cited by 8 papers.
What it found
Each row is one number read from the abstract, on the scale the paper reported it, with its interval. Left of the dashed line favours the treatment, right favours the comparator. Under each row is the sentence it came from. New to these charts? A ten-minute tutorial.
The abstract states no effect estimate the extractor could read, or names no intervention and outcome on the map, so this paper lights no cell and moves no belief. It is still indexed, cited and linked below.
The trial behind it
Trials whose registry record cites this paper, or whose number appears in the abstract. A trial that started after this paper was published is citing it as background, not reporting it.
Neither the registry nor the abstract names a trial number. If this is a trial report, that itself is worth knowing.
Who cites it
8 citing papers in PubMed.
- Impact of negative-pressure room utilization in the emergency department on hospitalized pneumonia patients during the COVID-19 pandemic in Thailand.Acute and critical care · 2026Article
- Evaluation of the effectiveness of isolation training given to the caregivers of patients in isolation with different methods: a randomized controlled study.BMC nursing · 2025Article
- Hospital-borne hazardous air pollutants and air cleaning strategies amid the surge of SARS-CoV-2 new variants.Heliyon · 2024Review
- Article
- Designing Mobile Epidemic Prevention Medical Stations for the COVID-19 Pandemic and International Medical Aid.International journal of environmental research and public health · 2022Article
- Ventilation Performance Evaluation of a Negative-Pressurized Isolation Room for Emergency Departments.Healthcare (Basel, Switzerland) · 2022Article
- Energy performance and indoor airflow analysis of a healthcare ward designed with resource conservation objectives.Journal of building engineering · 2021Article
- Infection Control Improvement of a Negative-Pressurized Pediatric Intensive Care Unit.Healthcare (Basel, Switzerland) · 2021Article
Corrections and comments
PubMed lists nothing against this paper. Absence here is not a guarantee, only a check that was made.
Authors and funding
5 authors.
Funding
Abstract
Negative-pressurized isolation rooms have been approved effectively and applied widely for infectious patients. However, the outbreak of COVID-19 has led to a huge demand for negative-pressurized isolation rooms. It is critical and essential to ensure infection control performance through best practice of ventilation systems and optimum airflow distribution within isolation rooms. This study investigates a retrofitting project of an isolation room to accommodate COVID-19 patients. The field measurement has been conducted to ensure the compliance with the design specification from the CDC of Taiwan. The pressure differentials between negative-pressurized isolation rooms and corridor areas should be at least 8 Pa, while the air change rate per hour (ACH) should be 8-12 times. Computational fluid dynamics (CFD) is applied to evaluate the ventilation performance and contamination control. Different layout arrangements of exhaust air have been proposed to enhance the ventilation performance for infection control. A simple projected air-jet curtain has been proposed in the simulation model to enhance extra protection of medical staff. The resulting ventilation control revealed that the contamination control can be improved through the minor adjustment of exhaust air arrangement and the application of an air-jet curtain.